Application of Low-voltage Active Filter in Hospital Buildings

1 Introduction

In order to improve the level of medical services, new and complex advanced medical equipment such as nuclear magnetic resonance, CT scanners, X-ray machines, and hemodialysis machines have been continuously introduced, and various energy-saving lighting equipment, inverter air conditioners, and elevator equipment have been put into use. These devices are non-linear devices that generate a large number of high-order harmonics during operation, causing some interference to the power distribution system and medical equipment. At the same time, these advanced medical devices have high-end computer components and a large number of high-sensitivity microelectronic devices. They have high requirements on the power quality of the power supply, and are very sensitive to voltage fluctuations and harmonics of the power. Severe power harmonic problems can cause medical problems. Damage to equipment can even lead to medical accidents.

2 Harmonic Source, Harmonic Characteristics and Harm Harm Analysis of Hospital Building Power Supply System

2.1 Sources of Harmonics

Main classification

Facility equipment name

Building facilities

Elevator equipment

central aircon system

Fire pump

lighting device

Medical Facilities

Operating room, laminar flow system

ICU, delivery room, neonatal care unit, hemodialysis center, etc.

Preparations, samples, blood preservation and freezing facilities

Hospital office automation facilities

Medical diagnostic equipment

The main diagnostic equipment, such as spiral CT machine, color Doppler, nuclear magnetic resonance apparatus, laparoscope, electroencephalogram machine, chromatograph, various function detection instruments, etc.

The main treatment equipment, such as ventilator, hyperbaric oxygen chamber, various monitors, laser therapeutic apparatus, etc.

2.2 Characteristics of Harmonics

Harmonic source load type

Harmonic current times

Harmonic current distortion rate

Lighting fixtures, computers, etc.

3,5,7,9, etc. (2n+1) times

(7~10)%

Electronic detection equipment, operating room, gamma knife, etc.

3,5,7,9, etc. (2n+1) times

(10~15)%

CT, magnetic resonance, DSA, etc.

3,5,7,9, etc. (2n+1) times

(30~40)%

Accelerators, X-ray machines, gastrointestinal machines, etc.

3,5,7,9, etc. (2n+1) times

(50~60)%

UPS, variable frequency ventilation equipment, elevators, etc.

5, 7, 9, 11 etc. (6n + 1) times

(25~35)%

2.3 Harmonic hazard analysis

2.3.1 Harmonic Harm to Distribution System

Increase the additional loss of power components and cause fire; affect the normal operation of electrical equipment; cause grid resonance; make relay protection malfunction, electrical measurement error is too large; so that the industrial control system crashes.

2.3.2 Harmonic harm to medical equipment

Loss of synchronization and data errors caused by devices that rely on microprocessor technology; directly endanger the safety of internal electronic circuits of devices, resulting in breakdown or discharge; and affect the performance and accuracy of precision medical devices.

3 National standards for power grid harmonics

The currently adopted power quality (harmonic) assessment standards are mainly China's national standard “Power Quality: Harmonics in the Public Power Grid” (GB/T14549-1993). The standards stipulate clearly the current and voltage distortion rate in the power grid, and also serve as Harmonic evaluation, an important basis for governance.

Table 1: National Harmonics Voltage Standards for Power Grids: Quoted in (GB/T14549-1993)

Grid nominal voltage (kV)

Total harmonic distortion (%)

Each harmonic voltage content (%)

Odd times

Even

0.38

5.0

4.0

2.0

6

4.0

3.2

1.6

10

35

3.0

2.4

1.2

66

110

2.0

1.6

0.8

Table 2: Allowable values ​​of harmonic currents injected into the common connection point of the grid: cited in (GB/T14549-1993)

Nominal electricity
Pressure (kV)

Short circuit

Capacity (MV.A)

Harmonic Times and Permissible Harmonic Current (A)

2

3

4

5

6

7

8

9

10

11

12

13

0.38

10

78

62

39

62

26

44

19

twenty one

16

28

13

twenty four

10

100

26

20

13

20

8.5

15

6.4

6.8

5.1

9.3

4.3

7.9

14

15

16

17

18

19

20

twenty one

twenty two

twenty three

twenty four

25

0.38

10

11

12

9.7

18

8.6

16

7.8

8.9

7.1

14

6.5

12

10

100

3.7

4.1

3.2

6

2.8

5.4

2.6

2.9

2.3

4.5

2.1

4.1

4 ANAPF low voltage active filter application in hospital building

4.1 Introduction to Active Filter Applications

The newly-built outpatient inpatient complex of a large-scale top-three hospital has a total of four 2000kVA and one 1600kVA transformers and one 800kW diesel generator, according to the load rate of the transformer's non-linear load equipment and the corresponding harmonic distortion rate. The harmonic currents are calculated using the simultaneous use rate of each nonlinear device, and five ANAPF active filters with different capacity specifications are configured.

The following is a detailed description of the comparative analysis of the power quality test conditions of the distribution system before and after the operation of the 1# ANAPF active filter. The load of 1# transformer is mainly lighting, elevators, submersible sewage pumps, and computer centers.

4.1.1 Data before and after the active filter is put into operation

(1) The distortion of the current waveform before the input of the active power filter is serious. The harmonic content of the three-phase current is respectively 19.7%, 27.8%, and 26.6%. The three-phase currents are 45A, 40A, and 64A, and the neutral current is 37A.

(2) The distortion of the current waveform after the input of the active filter is significantly improved, and the harmonic content of the three-phase current is significantly reduced, which is 2.9%, 2.8%, and 3.4%, and the three-phase currents are 47A, 48A, and 47A, respectively. The current is 5A.

(3) The current waveform is significantly improved. After the filter is used, the current waveform is approximately in the form of a sinusoidal wave. Harmonic control work has achieved the desired goal and effect.

4.1.2 Test Record Data Before and After the Active Filter Is Put into Operation

     

4.2 The significance of active filter application in hospital buildings

Protecting the safety of medical electrical equipment, purifying the power supply, protecting the power factor compensation equipment, preventing the malfunction of the protection device, reducing the power consumption, and expanding the power supply capacity of the transformer and the generator.

4.3 Active Filter Main Specifications

Wiring

Three-phase three-wire or three-phase four-wire

Access voltage

3×380V ±10%

Access frequency

50Hz ±2%

Dynamic compensation response time

Dynamic response <4ms, full response time <20ms;

On-off level

10kHz

Function settings

Only harmonics are compensated, only reactive power is compensated, both harmonics are compensated and reactive power is compensated; manual and automatic switching are performed.

Harmonic compensation times

2-21 times

Type of protection

DC over-voltage IGBT over-current device temperature protection

Overload protection

Automatic current limit in the set value, no overload occurs

cooling method

Smart air cooling

noise

< 65db (in the cabinet and operating in the rated state)

Working temperature

-10°C to +45°C

Working environment humidity

<85%RH non-condensing

Installation occasion

Indoor installation

Altitude

≤1000m (for use at higher altitudes)

Incoming and outgoing ways

Down in and out

Protection level

IP21

Intelligent communication interface

RS485/MODBUS-RTU

Remote monitoring

Optional

Overall size (mm)

(W×D×H)

30A

50A

75A

100A

600×500×1500

600×500×1500

600×500×1800

800×600×2200

Weight (kg)

Three-phase four-wire

Three-phase three-wire

30A, 50A

75A, 100A

30A, 50A

75A, 100A

280

360

240

290

4.4 Active Filter Quotation and Component List

Model Number: ANAPF100-400/B

Reference price: 120,000 yuan/set

The main product details:

No.

Name

Model number

Quantity

1

APF electrical cabinet

800X600X2200

1

2

Converter

APFCOV-CVT100

1

3

Controller

APFMC-C100

1

4

Reactor

APF-RE.(S)DG-100

1

5

Active current transformer

LT208-S7

3

6

filter

DL-1TH1

2

7

breaker

CVS160FTM160D4P3D

1

8

Contactor

LC1D150M7C

1

9

MCB

NDM1-63C32

1

10

Intermediate relay

MY4NAC

2

11

R type transformer

R320-0.38/0.22

1

12

Harmonic Detector

ACR350EGH

1

13

wire

16mm2

Some

14

wire

4mm2

Some

5 Conclusion

This article analyzes the harmonic source, harmonic characteristics and hazards of hospital buildings, and compares the situation before and after active power filter input and application through active filter applications in a low-voltage distribution system of a large hospital. Harmonic filter control technology is one of the effective means to improve the power quality of the power supply. The generated harmonics can be controlled within the minimum range to achieve scientific and rational use of electricity, inhibit power grid pollution, improve power quality, and ensure the safety of medical equipment. .

【references】

[1] GB/T 14549-1993 "Power Quality: Harmonics in Public Grids"

[2] Shanghai Ankerui Electric Co., Ltd. Product Manual. 2013.01.

[3] doc88.com "" hospital industry "distribution system harmonic control case"


Rubber Pad

Rubber Pad,Black Railway Rubber Pad,High-Elastic Rail Pads,Rubber Pad For Railway

Anyang Railway Equipment CO.,Ltd , https://www.ayrailwayat.com